Refer to:
‘Installation Instructions for CFSD Series
Corridor Ceiling Dampers’ (Part #461335) for
additional details.
Detail ‘A’: Forming Channel
Figure #1: Opening Preparation Detail (top view)
Notes
1. Gypsum panels must be screwed 12 in. (305mm) O.C.
(on center) maximum to all stud and runner flanges
surrounding opening with 1
5
/8 in. (41mm) drywall screws
or fasteners designated by the appropriate corridor
ceiling design. (See Figure 1 for Opening Preparation
Details).
2. Retaining angles must be attached to the sleeve (not the
partition). (See Figure 2 and 3.)
- Retaining angles must be a minimum of 20 gauge
(1mm) steel and have a minimum of 1
1
/2 in. x 1
1
/4 in.
(38mm x 32mm) legs.
- Retaining angles must be attached to the sleeve using
one of the methods shown below.
- tack or spot welds
- #10 sheet metal screws
-
1
/4 in. x 20 bolts and nuts
-
3
/16 in. (4.7mm) steel rivets
- Quick-Lock Joints
- A minimum of two connections per side, top, and
bottom (12 in. [305mm] on center maximum).
- Retaining angles must overlap the partition a minimum
of 1 in. (25mm)
- A minimum
3
/4 in. x 20 gauge (19mm x 1mm) flange
termination may be used in lieu of retaining angles on
the corridor side of the damper sleeve.
Cut here and
bend down
Copyright © 2013 Greenheck Fan Corporation
463832 Tunnel Corridor Supplement Rev. 5 January 2013
24" O.C.
Maximum
Side
Runner
Detail ‘A
Side
Runner
2”
2”
12”
AA
Two
Panhead
Screws
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555, 555S (Listing #R13317)
Document Number 463832
INSTALLATION INSTRUCTION SUPPLEMENT
CFSD Series
1 Hour Corridor Ceiling Fire Smoke Dampers
Metal Stud Framing for Fire Dampers in Tunnel Corridor
Shaftwall Ceilings
Retaining
angle
5
/8" UL Classified Gypsum
Wallboard min.
20 ga. steel
stud
Damper
Sleeve
Angle
Fastener
(see Note 2)
1”
Min.
2
1
2” min. stud
Screws
2
1
2” min.
stud
Section A-A
Figure #2: 1 Hour Shaftwall Rating (‘C’ Channel)
Retaining
angle
5
/8" UL Classified Gypsum
Wallboard min. (see UL
Rated Wall Design for
Additional Details)
20 ga. steel
J-Runner
C-H Stud
Damper
Sleeve
Angle
Fastener
(see Note 2)
1”
Min.
2
1
2” 20 ga.
steel J-Runner
Screws
2
1
2” min.
stud
Section A-A
Figure #3: 1 Hour Shaftwall Rating (‘C-H’ Channel)
®